Q: I bhfianaise P₀ agus Pₖ ó thástálacha, conas a dhéanaim éifeachtúlacht a ríomh ag leibhéil éagsúla ualaigh?
A: Éifeachtúlacht η=P_out / (P_out + P₀ + ² × Pₖ) × 100%, i gcás ina=fachtóir ualach.
Sampla: 10 claochladán MVA, P₀=12 kW, Pₖ=85 kW:
|
Luchtaigh |
|
Aschur (kW) |
P₀ (kW) |
²×Pₖ (kW) |
η (%) |
|
25% |
0.25 |
2,500 |
12 |
5.3 |
99.31 |
|
50% |
0.50 |
5,000 |
12 |
21.3 |
99.34 |
|
75% |
0.75 |
7,500 |
12 |
47.8 |
99.21 |
|
100% |
1.00 |
10,000 |
12 |
85.0 |
99.04 |
|
120% |
1.20 |
12,000 |
12 |
122.4 |
98.89 |
Éifeachtúlacht uasta ag=√(P₀ / Pₖ)=0.376 → ~37.6% ualach.
Caighdeáin éifeachtúlachta fuinnimh:
• IEC 60076-20: Aicmí EEI A (is airde) → D.
• Éiceadhearadh an AE 2019/1783: Sraith 2 (2021), Sraith 3 (2025–27).
• DOE 10 CFR Cuid 431: riail nua le héifeacht Meitheamh 2026.
• GB 20052-2020 (tSín): Grád 1 (is airde) → 3 .
• IS 1180 (India): BEE Star Rating 1–5.
Cur chuige TCO: TCO=Praghas + A × P₀ + B × Pₖ
A ≈ $3,000–8,000/kW (gan-chostas ualaigh chaipitlithe).
B ≈ $500–2,000/kW (costas ualaigh caipitlithe).